Handheld Power Quality Analyzer

1000V/3000A Power Quality Analyzer

Model: SA2100

Features:

●Safety: CAT III 1000V / CAT IV 600V

●Standards: IEC61000-4-30 (2008) S class, EN50160 (2007)

●Easy operation to capture the power quality problem

●Single-phase 2 W/Single-phase 3 W/ 3-phase 3 W/ 3-phase 4 W

●Display: Run Chart, Bar Chart, Vector Graphic, Waveform,Event List, Readings

●8G Memory Card to make the long-term measuring data storage

●Support USB Interface

●Support LAN Interface

Specification:

Specifications Measurement Range Resolution Accuracy

Voltage/Current/Frequency

Channel 3-phase line input+1neutral line input
Vrms(dc+ac) 1~1000Vrms 0.1Vrms ±5%
Vpk 1~1400Vpk 0.1Vpk ±5%
V(CF) 1.0~>2.8 0.01 ±5%
Arms 1~3000A 1A ±1% ± 5digits
1~300A 0.1A ±1% ± 5digits
Apk 1~4000Apk 1A ±1% ± 5digits
A(CF) 1~10 0.01 ±5%
Frequency 42.5~57.5Hz(50Hz nominal) 0.01Hz ±0.01%
51~69Hz(60Hz nominal) 0.01Hz ±0.01%

Dips & Swells

Vrms1/2 0~200% of nominal voltage 0.1Vrms ±1%
Arms1/2 1~3000A 1A ±1% ±5 counts
1~300A 0.1A ±1% ±5 counts
Threshold levels Programmable thresholds in percent of nominal voltage
Event detection based upon ½ cycle rms voltages
Captures Dips,Swells Interruptions and Rapid Voltage Changes
Duration hhh,mm,ss,mmm 0.5cycle 1cycle

Harmonic

Harmonic Order 1~50
Inter-Harmonic Order 1~49
Voltage 0.0~100.0% 0.10% ±0.1%±nx0.1%
Current 0.0~100.0% 0.10% ±0.1%±nx0.1%
THD 0.0~100.0% 0.10% ±2.5%
DC Relative 0.0~100.0% 0.10% ±2%
Frequency 0~3500Hz 1Hz 1Hz
Phase -360°~0° ± nx1.5°

Power And Energy

Active Power/Apparent Power/Reactive Power 1.0~20.00MW 0.1kW ±1.5±10counts
Energy 0.00kWh~200GWh 10Wh ±1.5±10counts
Power Factor 0~1 0.01 ±0.03

Flicker

Pst(1min),Pst,Plt,PF5 0.00~20.00 0.01 ±5%

Unbalance

Voltage 0.0~5.0% 0.10% ±0.5%
Current 0.0~20.0% 0.10% ±1%
Voltage Phase Angle -360°~0° ±2digits
Current Phase Angle -360°~0° ±5digits

Voltage Transient

Vpk ±6000Vpk 1V ±15%
Vrms 10~1000Vrms 1V ±2.5%
Min. Tested Time 50us
Sampling Rate 20kS/s

Inrush Current

Arms(AC+DC) 0~3000Arms 0.1 ±1%±5digits
Inrush Duration 6s~32min selectable 10ms ±20ms

Logger

Recording Parameter,duration time and time interval can be set by user,which can be export on PC
Memory 8G
Max. recording time 1 year

System Monitor

Parameters Vrms,Arms,Harmonic Volts,THD Volts,Plt,Vrms1/2,Arms1/2,Vneg,Hz,dips and swells,

unbalance

Record Time 2h~7days
Record Event Number >10000
Limits According EN50160 or customer definable

General Characteristics

Power AC220V(1±10%),50Hz(1±5%),≤10VA
Interface USB_HOST, LAN
Display 5.6′ TFT LCD, 320*240
Battery 7.4V, 4.4Ah, >7 hours working time
Dimension & Weight 262×173×66mm,1.6kg