Handheld Power Quality Analyzer

1000V/3000A Power Quality Analyzer
Model: SA2100
Features:
●Safety: CAT III 1000V / CAT IV 600V
●Standards: IEC61000-4-30 (2008) S class, EN50160 (2007)
●Easy operation to capture the power quality problem
●Single-phase 2 W/Single-phase 3 W/ 3-phase 3 W/ 3-phase 4 W
●Display: Run Chart, Bar Chart, Vector Graphic, Waveform,Event List, Readings
●8G Memory Card to make the long-term measuring data storage
●Support USB Interface
●Support LAN Interface
Specification:
| Specifications | Measurement Range | Resolution | Accuracy |
|
Voltage/Current/Frequency |
|||
| Channel | 3-phase line input+1neutral line input | ||
| Vrms(dc+ac) | 1~1000Vrms | 0.1Vrms | ±5% |
| Vpk | 1~1400Vpk | 0.1Vpk | ±5% |
| V(CF) | 1.0~>2.8 | 0.01 | ±5% |
| Arms | 1~3000A | 1A | ±1% ± 5digits |
| 1~300A | 0.1A | ±1% ± 5digits | |
| Apk | 1~4000Apk | 1A | ±1% ± 5digits |
| A(CF) | 1~10 | 0.01 | ±5% |
| Frequency | 42.5~57.5Hz(50Hz nominal) | 0.01Hz | ±0.01% |
| 51~69Hz(60Hz nominal) | 0.01Hz | ±0.01% | |
|
Dips & Swells |
|||
| Vrms1/2 | 0~200% of nominal voltage | 0.1Vrms | ±1% |
| Arms1/2 | 1~3000A | 1A | ±1% ±5 counts |
| 1~300A | 0.1A | ±1% ±5 counts | |
| Threshold levels | Programmable thresholds in percent of nominal voltage | ||
| Event detection based upon ½ cycle rms voltages | |||
| Captures Dips,Swells Interruptions and Rapid Voltage Changes | |||
| Duration | hhh,mm,ss,mmm | 0.5cycle | 1cycle |
|
Harmonic |
|||
| Harmonic Order | 1~50 | ||
| Inter-Harmonic Order | 1~49 | ||
| Voltage | 0.0~100.0% | 0.10% | ±0.1%±nx0.1% |
| Current | 0.0~100.0% | 0.10% | ±0.1%±nx0.1% |
| THD | 0.0~100.0% | 0.10% | ±2.5% |
| DC Relative | 0.0~100.0% | 0.10% | ±2% |
| Frequency | 0~3500Hz | 1Hz | 1Hz |
| Phase | -360°~0° | 1° | ± nx1.5° |
|
Power And Energy |
|||
| Active Power/Apparent Power/Reactive Power | 1.0~20.00MW | 0.1kW | ±1.5±10counts |
| Energy | 0.00kWh~200GWh | 10Wh | ±1.5±10counts |
| Power Factor | 0~1 | 0.01 | ±0.03 |
|
Flicker |
|||
| Pst(1min),Pst,Plt,PF5 | 0.00~20.00 | 0.01 | ±5% |
|
Unbalance |
|||
| Voltage | 0.0~5.0% | 0.10% | ±0.5% |
| Current | 0.0~20.0% | 0.10% | ±1% |
| Voltage Phase Angle | -360°~0° | 1° | ±2digits |
| Current Phase Angle | -360°~0° | 1° | ±5digits |
|
Voltage Transient |
|||
| Vpk | ±6000Vpk | 1V | ±15% |
| Vrms | 10~1000Vrms | 1V | ±2.5% |
| Min. Tested Time | 50us | ||
| Sampling Rate | 20kS/s | ||
|
Inrush Current |
|||
| Arms(AC+DC) | 0~3000Arms | 0.1 | ±1%±5digits |
| Inrush Duration | 6s~32min selectable | 10ms | ±20ms |
|
Logger |
|||
| Recording | Parameter,duration time and time interval can be set by user,which can be export on PC | ||
| Memory | 8G | ||
| Max. recording time | 1 year | ||
|
System Monitor |
|||
| Parameters | Vrms,Arms,Harmonic Volts,THD Volts,Plt,Vrms1/2,Arms1/2,Vneg,Hz,dips and swells,
unbalance |
||
| Record Time | 2h~7days | ||
| Record Event Number | >10000 | ||
| Limits | According EN50160 or customer definable | ||
|
General Characteristics |
|||
| Power | AC220V(1±10%),50Hz(1±5%),≤10VA | ||
| Interface | USB_HOST, LAN | ||
| Display | 5.6′ TFT LCD, 320*240 | ||
| Battery | 7.4V, 4.4Ah, >7 hours working time | ||
| Dimension & Weight | 262×173×66mm,1.6kg | ||